SYSTEM
PERFORMANCE CRITERIA (Tested on Actual Understructure)
|
|||||||
|
Panel |
U/S | SYSTEM
WEIGHT (lbs/ft²) |
STATIC
LOADS |
ROLLING
LOADS |
IMPACT
LOADS (lbs) |
||
| Design
Loads* (lbs) |
Safety
Factors* (min 2.0) |
10
Passes (lbs) |
10,000
Passes (lbs) |
||||
WC5000 |
Cornerlock |
6.9 |
1000 |
PASS |
1000 |
700 |
150 |
WC5000 |
Snap-Tite/ Bolt-Tite |
7.4 |
1000 |
PASS |
1000 |
700 |
150 |
| WC5000 | Heavy Duty | 7.6 |
1250 |
PASS |
1200 |
875 |
150 |
| WC6000 | Heavy Duty | 8.28 |
1500 |
PASS |
1500 |
1050 |
150 |
*For more information on design load download the Design Load Technical Bulletin. All other tests are conducted under CISCA’s recommended test procedures for access floors.