ConCore System
Performance Chart
The Performance Charts below are divided into two sections to help you evaluate the overall performance of the systems. The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.
| SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure) | |||||||
| Panel | U/S |
SYSTEM WEIGHT (lbs/ft²) |
STATIC LOADS |
ROLLING LOADS |
IMPACT
LOADS (lbs) |
||
Design
Loads* (lbs) |
Safety
Factors* (min 2.0) |
10
Passes (lbs) |
10,000
Passes (lbs) |
||||
| ConCore 1000 | Posilock |
7.5 |
1000 |
PASS |
800 |
600 |
150 |
| ConCore 1250 | Posilock |
8.5 |
1250 |
PASS |
1125 |
875 |
150 |
| ConCore 1500 |
Posilock |
9.0 |
1500 |
PASS |
1250 |
1000 |
150 |
| SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure) | |||||||
| Panel | U/S |
SYSTEM WEIGHT (lbs/ft²) |
STATIC LOADS |
ROLLING LOADS |
IMPACT
LOADS (lbs) |
||
Design
Loads* (lbs) |
Safety
Factors* (min 2.0) |
10
Passes (lbs) |
10,000
Passes (lbs) |
||||
| ConCore 1000 | Bolted Stringer |
9.0 |
1000 |
PASS |
800 |
600 |
150 |
| ConCore 1250 | Bolted Stringer |
10.0 |
1250 |
PASS |
1000 |
875 |
150 |
| ConCore 1500 |
Bolted Stringer |
10.5 |
1500 |
PASS |
1250 |
1000 |
150 |
| ConCore 2000 | Bolted Stringer |
11.5 |
2000 |
PASS |
1500 |
1250 |
150 |
| ConCore 2500 | Bolted Stringer |
12.0 |
2500 |
PASS |
2000 |
2000 |
150 |
| ConCore 3000 | 2" Deep Bolted Stringer |
13 |
3000 |
PASS |
2700 |
2400 |
200 |
*For more information on design load download the Design Load Technical Bulletin. All other tests are conducted under CISCA’s recommended test procedures for access floors.