Tate Access Floors

only search tateinc.com
bottom

Aluminum System

Performance Chart


The Performance Charts below are divided into two sections to help you evaluate the overall performance of the systems. The System Performance Criteria are the most important to consider because they represent the performance in a typical installation.


FF1250 SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel
U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
10 Passes
(lbs)
10,000 Passes
(lbs)
Solid Panels
Bolted Stringer/
Stringerless/
Cornerlock

6.5

1250
2.0
1000
1000
150
Perf Panels
Bolted Stringer/
Stringerless/
Cornerlock
6.25
1250
2.0
1000
1000
150
Grates
Bolted Stringer/
Stringerless/
Cornerlock
7.25
1250
2.0
1000
1000
150

FF3000 SYSTEM PERFORMANCE CRITERIA (Tested on Actual Understructure)
Panel
U/S SYSTEM WEIGHT
(lbs/ft²)
STATIC LOADS
ROLLING LOADS
IMPACT LOADS
(lbs)
Design Loads*
(lbs)
Safety Factors*
(min 2.0)
10 Passes
(lbs)
10,000 Passes
(lbs)
Solid Panels
Bolted Stringer/
Stringerless/
Cornerlock

7.60

2250
2.0
2000
2000
200
Perf Panels
Bolted Stringer/
Stringerless/
Cornerlock

7.40

2000
2.0
1500
2000
100

*For more information on design load download the Design Load Technical Bulletin.  All other tests are conducted under CISCA’s recommended test procedures for access floors.
 